Timeguard TX2450C 50A 30mA Solid Neutral RCBO C Curve 6kA, 30mA Type A, Uni-Directional
Estimated delivery time: Estimated delivery tomorrow*
Description
The Timeguard TX2450C is a 50A, 30mA Type A RCBO with a C-curve overcurrent characteristic and 6kA breaking capacity. It combines overload, short-circuit and residual-current protection for an individual circuit in a compatible Timeguard TX series consumer unit.
This is the solid-neutral, unidirectional version. Check the complete specification when ordering a replacement, because other RCBOs with the same current rating can have different tripping, neutral-switching and power-flow arrangements.
Choose the correct current rating and curve
The 50A rating must suit the circuitβs cable, connected equipment and installation conditions. It should not be selected simply as an upgrade to a lower-rated protective device.
C-curve has a higher instantaneous magnetic operating threshold than an equivalent B-curve device. This can accommodate brief starting currents where the equipment and circuit design support its use. The rated circuit current remains 50A.
The corresponding B-curve model is TX2450, so the final letter matters when selecting the correct version.
Understand solid neutral and unidirectional operation
With a solid neutral, the neutral remains connected when the protected line pole opens. The installationβs isolation requirements must therefore be assessed separately.
Unidirectional operation means supply and load connections must follow the manufacturerβs markings. This model must not be selected for a circuit requiring reverse or bidirectional power flow.
The 30mA Type A residual-current function responds to sinusoidal AC and pulsating DC residual currents.
Compact dimensions and clearly specified connections
The single-module housing measures 18mm wide Γ 85mm high Γ 73mm deep and mounts onto a 35mm DIN rail.
Top terminals accept conductors up to 10mmΒ², with a specified tightening torque of 1.2Nm. Bottom terminals accept up to 25mmΒ², with a tightening torque of 2.5Nm. Terminal blanking plates help prevent incorrect cable or busbar insertion.
A test button and contact position indicator are included. The RCBO can also be removed without removing the busbar once the assembly has been safely isolated.
Timeguard provides a five-year guarantee, subject to its applicable terms. Manufacturer compatibility is limited to Timeguard TX series consumer units.