Timeguard TX2340C 40A 6KA Type C Curve MCB

SKU TX2340C
Original price £2.20 - Original price £2.20
Original price
£2.20 inc VAT £1.83 exc VAT
£2.20 - £2.20
Current price £2.20 inc VAT £1.83 exc VAT inc VAT £1.83 exc VAT

Estimated delivery time: Estimated delivery tomorrow*

Description

The Timeguard TX2340C 40A C-curve MCB provides overload and short-circuit protection for an individual electrical circuit. Designed specifically for Timeguard TX series consumer units, this single-pole miniature circuit breaker has a 6kA breaking capacity and occupies one module.

It is an option for electricians selecting protective devices for a compatible installation or replacing an existing breaker where the circuit requires 40A C-curve protection.

Understanding the C-curve characteristic

A C-curve MCB has a higher instantaneous magnetic operating threshold than an equivalent B-curve device. This can accommodate brief starting currents where the connected equipment and circuit design support its use.

The current rating remains 40A. Selecting C-curve does not increase the circuit’s permitted continuous load. Cable protection, equipment characteristics and the fault current needed to achieve the required disconnection time must all be considered.

Practical terminal and maintenance features

The terminal cages include blanking plates that help prevent a cable or busbar from being inserted outside the clamp. Maximum terminal capacity is 25mm², with a manufacturer-specified tightening torque of 2.5Nm.

A contact position indicator provides a visible indication of contact status. The breaker can also be removed without removing the busbar, helping with maintenance once the consumer unit has been safely isolated.

Compact fitting and a five-year guarantee

Measuring 18mm wide × 81mm high × 73mm deep, the breaker mounts onto a 35mm DIN rail. Timeguard provides a five-year guarantee, subject to its applicable terms.

Check the complete code before ordering: TX2340C is C-curve, while TX2340 is B-curve. Manufacturer compatibility is limited to Timeguard TX series consumer units.

Where residual-current protection is required, an appropriate RCD or RCBO arrangement must also form part of the installation design.

FAQ's

What is the Timeguard TX2340C?

It is a 40A C-curve single-pole miniature circuit breaker with a 6kA breaking capacity. It provides overload and short-circuit protection within compatible Timeguard TX consumer units.

Is TX2340C definitely C-curve?

Yes. The manufacturer’s datasheet lists this exact code in the C-curve range. The B-curve bullet on the product page conflicts with the heading and datasheet.

How does TX2340C differ from TX2340?

TX2340C is C-curve; TX2340 is B-curve. Both are rated at 40A, but their instantaneous magnetic operating characteristics differ.

What does C-curve mean?

Under BS EN 60898-1, the C-curve instantaneous magnetic operating band is 5–10 times rated current. It has a higher magnetic operating threshold than B-curve.

What is the instantaneous operating band for this 40A C-curve MCB?

The standard band corresponds to 200–400A. This describes short-duration magnetic operation, not a permitted continuous load.

Will it trip immediately if the current exceeds 40A?

Not necessarily. Operating time depends on the size and duration of the overcurrent and the breaker’s time-current characteristic.

Can I replace a 40A B-curve breaker with this model?

Only after an electrician checks the circuit design. Changing the characteristic affects the fault current required for rapid operation and may alter whether the required disconnection conditions are met.

Will C-curve stop tripping when equipment starts?

It may be appropriate where verified starting current is the cause and the circuit supports C-curve protection. It will not correct an overload, damaged wiring or faulty equipment.

Is it suitable for motors, lighting drivers or other equipment with inrush current?

Suitability depends on the equipment manufacturer’s guidance, starting characteristics and circuit design. The C-curve marking alone does not approve a particular load.