Ovia OV2071AG25EM Inceptor Murus 25W LED Emergency Wall Pack – 3-Hour Backup, CCT Switchable, IP66 IK10, Anthracite Grey

The Ovia OV2071AG25EM Inceptor Murus LED emergency wall pack combines everyday exterior illumination with battery-backed emergency lighting. Featuring a 25W LED module, selectable colour temperature and an anthracite grey finish, this wall-mounted luminaire delivers up to 3,000 lumens during normal operation. Its integrated emergency pack provides a minimum three-hour backup duration, helping maintain illumination when the normal lighting supply fails.

The integrated CCT selector allows your electrician to choose between 3000K warm white, 4000K cool white and 6000K daylight. This makes it easier to match surrounding fittings or agree the preferred light appearance during installation.

For property owners upgrading entrance lighting or contractors specifying commercial exterior wall lights, three selectable settings provide flexibility within one product reference.

During emergency operation, Ovia specifies 410 lumens and a minimum three-hour duration. This provides a separate performance figure for assessing illumination during a power failure.

The fitting can be wired for maintained or non-maintained operation, allowing the installer to configure its behaviour around the project’s requirements. For an emergency lighting layout, the battery-powered output should be considered alongside mounting height, route dimensions and the locations requiring illumination.

Specification
  • Ingress Protection - IP66
  • Impact Rating (IK) - 10
  • Mounting - Wall
  • Warranty (Years) - 5
  • Battery Warranty (Years) - 4
  • Input Voltage & Frequency (V~ / Hz) -Β 220-240 50
  • Surge Protection Installed - Yes
  • Circuit Wattage (W) - 27
  • LED Wattage (W) - 25
  • Input Current (mA) -Β 0.109
  • Inrush Current -Β 15A (183Β΅S)
  • Power FactorΒ >0.9
  • Driver Information -Β Integrated (Tridonic)
  • Input Terminations -Β 4 Pole Push-fit Terminals
  • Colour Temperature (K) - 3000/4000/6000
  • Typical Luminous Flux (lm) - 2500/3000/2500
  • Beam Angle (Β°) -Β 80 x 140
  • Emergency Luminous Flux (lm) - 410
  • Colour Rendering Index (CRI)Β >80
  • Flicker Free - Yes
  • LED Lifetime (L70) (Hours) - 50.000
  • Dimmable - No
  • Battery Specification -Β Li-Ion 2600mAh 3.7V
  • Minimum Duration (Hours) - 3
  • Battery Warranty (Years) - 4
Product Dimensions

267.4 (W) x 147 (D) x 332.6 (H) (mm)

FAQ's

Where would I use the Ovia OV2071AG25EM emergency wall pack?

It can be considered for wall-mounted entrance, walkway and perimeter lighting where emergency backup is required. Suitability depends on the mounting position, environmental conditions and lighting design. For an escape route, your designer should assess the 410-lumen emergency output against the illumination required at ground level.

Which colour setting gives the brightest light?

The 4000K cool white setting provides 3,000 lumens, the highest stated normal output. Both the warm white and daylight settings provide 2,500 lumens. Your electrician selects the required colour temperature using the CCT switch, allowing the fitting to be matched to the lighting scheme.

Will it still produce 3,000 lumens during a power failure?

The manufacturer specifies 410 lumens during emergency operation, with a minimum three-hour duration. The higher normal-output figures apply during mains-powered operation. Emergency lighting calculations should therefore use the emergency performance data when assessing coverage during a supply failure.

Can I install this emergency wall light somewhere exposed to freezing temperatures?

Ovia specifies 0Β°C to +50Β°C for this emergency model. A location falling below freezing would be outside that published operating range. Check the expected winter temperature at the fitting’s position; the IP66 rating describes ingress protection and does not extend its temperature rating.

8What supply and mounting details should an electrician check?

The fitting requires 220–240V AC at 50Hz and has Class I construction requiring an earth connection. It includes four-pole push-fit terminals. The backplate supports BESA/conduit-box and trunking arrangements, so installers should assess the existing supply route, mounting surface and emergency operating configuration before installation.

Can the emergency battery be replaced, and which battery does it use?

Ovia’s current technical sheet identifies a 6.4V 1500mAh LiFePO4 battery, with OVEMB6415LIS-WP listed as the compatible replacement. When maintaining an existing fitting, match its battery specification, connector and product revision before ordering a replacement pack