Crabtree 380/A030 Starbreaker 80A Double Pole 30mA Type A RCD

SKU 380/A030
Original price £41.55 - Original price £41.55
Original price
£41.55 inc VAT £34.63 exc VAT
£41.55 - £41.55
Current price £41.55 inc VAT £34.63 exc VAT inc VAT £34.63 exc VAT
Availability:
43 in stock, ready to be shipped

Estimated delivery time: Next working day

Description

The Crabtree Starbreaker 380/A030 80A 30mA Type A RCCB is a high-quality residual-current circuit breaker designed for compatible Crabtree Starbreaker consumer units. It provides double-pole residual-current protection, simultaneously disconnecting both poles when a qualifying earth-leakage fault is detected.

Rated at 80A with 30mA residual-current sensitivity, the Crabtree 380/A030 is suitable for installations requiring additional protection against electric shock and earth-leakage faults. Its Type A detection characteristic is designed to respond to sinusoidal alternating residual currents and pulsating direct residual currents associated with many modern electrical appliances and electronic loads.

The RCCB is rated for 230V AC operation at 50Hz and has a rated insulation voltage of 400V. A 4kV impulse-withstand rating supports dependable performance within compatible fixed electrical-distribution systems subject to correctly designed installation conditions.

Specification
  • Number of poles 2
  • Rated voltage 230 V
  • Rated current 80 A
  • Rated fault current 0.03 A
  • Rated insulation voltage Ui 400 V
  • Rated impulse withstand voltage Uimp 4 kV
  • Mounting method DIN rail
  • Leakage current type A
  • Selective protection No
  • Frequency 50 Hz
  • Additional equipment possible No
  • With interlocking device No
  • Degree of protection (IP) IP20
  • Width in number of modular spacings 2
  • Connectable conductor cross section multi-wired 50 mm²
  • Product Standard/s BS EN 61008
  • CE Conformity Yes
  • WEEE Symbol Yes
  • UKCA Conformity Yes
  • Rated making and breaking capacity I∆m 6000 A
  • Rated residual making and breaking capacity Im 1000 A
  • Energy let through maximum 31 kA²s
  • Energy let through peak 4.7 kA