ESP MAG2P Fireline 2 Zone Polycarbonate Cased Conventional Fire Alarm Panel
SPECIFICATION:
- 2 programmable zones
- Active end of line monitoring and head removal
- 30 fire detectors per zone
- Unlimited number of call points per zone
- Integral sound alarm button
- 'Class change' facility
- Enable/disable security key
- One man walk test facility
- Volt free fire and fault change over relays
- Individual sounder circuit fault ID
- Individual zone/sounder isolate
- EN54 P2/4 compliant and CE certified
- Requires only 1 x 12v 7Ah battery
- ABS casing
- Max Detectors Per Zone - 20
- Thresholds for Zone Conditions - 0 - 2 mA (Fault condition)
- Sounder 1 - 24V (max 300mA fused)
- Sounder 2 - 24V (max 300mA fused)
- Fault/Fire Relay - Volt free 500mA @ 24V (max load)
- Auxiliary Output - 24VDC (300mA fused)
- Mains Fail Consumption - 50mA
- Mains Supply - y 230 VAC ± 10%
- Standby Supply - Up to 12V 7Ah (Battery Calculation Required)
- Power Availability - 0.7 amps
ESP MAG2P Fireline 2 Zone Polycarbonate Cased Conventional Fire Alarm Panel
SKU: MAG2P
£92.20Price
VAT Included
£76.83